Note 1:
1 Suitable for outdoor and indoor installation.
2 Aluminum connection bank
3 Including the lift guidance which only one reactor can be lifted once.
4 Gray insulation varnish can be painted after completion.
5 The dimension size is millimeter.
6 The applied standard is GB10229-1988/IEC 60076-6-2007.
7. Hot short-circuit current is 8KA/2 seconds.8 Mechanical peak current 20.4 KA.
9 Basic shock level 350KV.
10 The insulator shock level to ground 650kv.
11. Reactor Maximum weight is 5,700kg, and the support maximum weight is 1,300kg.
12. Earthquake horizontal acceleration is 0.3g.
13 Reactor natural frequency is 176.5Hz with windward side 14.5m2.
The minimum distance between reactors A=4064
The reactor field will cause the heating of adjacent ferromagnetic objects and additional electrodynamics force. This drawing recommends the magnetic field contour(MC),the influenced ferromagnetic objects mainly are closed loop such as earth grid, isolation iron wire gauze, concrete steel reinforcement etc.It must be paid particulate attention to that the reactor field will influence the adjacent electric induction equipments and must implement special field analysis if necessary.